Bollard does not work with the App
Standard reset procedure
Check if they can hear a clicking noise when they give a command with the app
Check if the light on the Brain is working correctly (it should be red and turn green when you restart the brain
Client should give any impulse by short circuiting the LO and COM port 18
Note: COM port is written on the board as a down arrow
When they short circuit that they should have a message displayed on the LED display saying OP (open) or CL (closed)
Check if you can use the Bollard with the remote control (if yes, something is wrong with the brain)
Do the Automatic learning process
Related Articles
How to connect Master and Slave bollard
Please look at the wiring diagram how to connect Master and slave bollard: Also some programming is needed: In this case you just install photocells for master bollard.
LE & LA Error on Parklio Bollard
Bollards are programmed not to work without photocells and if they are not installed you get LE or LA Error and Bollard can not work. - LE error means photocell 1 is not installed. - LA error means photocell 2 is not installed.
Bollard remotes adding and erasing
Please find all the instructions for adding and erasing bollard remotes:
Bollard photocells
Two pairs of photocells are always delivered together with Parklio Bollard device and connected to the control box using a UTP cable. Every photocell has its own transmitter that must be installed on site depending on the Bollard desired position. ...
Bollard Control Box Overview
Each bollard is delivered with a control box responsible for powering and controlling the device. The control box manages the electrical supply and communication required for the bollard to operate properly. Control Box Dimensions The dimensions of ...